Kleine-Tebbe, A. (1996) Earthquake Qualification Test of a Low-Voltage Switchgear System MNS. DLR-Interner Bericht. IB 232 96 C 11. 2 S.
Full text not available from this repository.
Abstract
The earthquake qualification of the low-voltage switch gear system was tested. The tests were carried out with sine beat excitation in the frequency range of 1-35 Hz with a distance of 1/3 oct. so that the envelope of all beats met with the given response spectra (IEC 68-2-57, Bulgarian Standard). Interferences in the system functions did not occur.